Electrical Performance Terms
Every cable datasheet lists electrical parameters — but knowing the numbers and understanding what they mean in the field are two different things. This is the most technically detailed module in the series, covering the five performance specifications that govern whether a cable run will be safe, code-compliant, and functional for its intended application. Each term gets a definition, a formula, an explanation of consequences, and a real-world scenario drawn from industrial and commercial electrical practice.
Ampacity — the thermal current ceiling — is governed by NEC Table 310.15(B) and must be derated for conduit fill, high ambient temperature, and bundled cables. Voltage drop — calculated as VD = I × R (DC) or I × Z (AC) — must not exceed 3% on branch circuits per NEC guidance, or equipment suffers. Impedance — the frequency-dependent total opposition to AC current — becomes critical in VFD cable runs and data cabling where impedance mismatch causes destructive reflected voltage waves. Capacitance (measured in pF/ft) acts as a low-pass filter in long instrumentation cable runs, degrading 4–20mA loop response and RS-485 communication at long distances. And inductance (measured in µH/ft) combined with cable capacitance creates LC resonant circuits in VFD motor leads — sometimes doubling peak voltage at the motor terminals and destroying winding insulation.
WHAT YOU'LL LEARN
- Ampacity: definition, NEC Table 310.15(B), and derating rules
- Voltage drop: VD = I×R formula and the 3%/5% NEC guideline
- Impedance: Z = √(R² + (XL−XC)²) and frequency dependence
- Capacitance: pF/ft, low-pass filter effect on 4–20mA and RS-485
- Inductance: µH/ft, LC resonance, and VFD motor lead voltage spikes
- Real-world scenarios: boiler room feeder, CNC machine run, VFD cable
- How to find all five values on a manufacturer's cable datasheet
- Quick-reference comparison table: all 5 terms, units, and gotchas